The performance test is carried out by measuring the pressure difference between the inlet and outlet of the fans. Subsequently, the pressure difference is used to read the airflow through the curve in the figure or to calculate the airflow using the equations respect to the type of air handling unit.
Before the measurement of the pressure difference is carried out it is important that:
If you have an AM150 or AMC150 generation 2 where the fans have been replaced to a newer type, please use the data for generation 3 given below.
The following figure and equations for AM 300 H/V are applicable for both extraction and supply.
Figure 5.1 and equation 5.1 to 5.6 for AM 300 are applicable extraction flow depending on position of ex-haust connection.
Figure 5.2 and equation 5.7 to 5.12 for AM 300 are applicable supply flow depending on position of supply connection.
The following figure and equations for AM 500 H are applicable for both extraction and supply.
The following figure and equations for AM 500 V are applicable for both extraction and supply.
The following figure and equations for AM 800 H/V are applicable for both extraction and supply.